Almost all electric power is generated, transmitted and used as three-phase AC (in Portuguese: sistema trifásico). Spin the generator and watch three voltages 120° apart travel down the lines to a load connected in wye (Y, star) or delta (Δ). Every meter is computed exactly with complex numbers: see why the line voltage is √3 times the phase voltage, why a balanced neutral carries no current and the total power is constant, size a capacitor bank for power-factor correction, break the neutral of an unbalanced load, and measure power with two wattmeters. Supplies of Brazil (127/220 V and 220/380 V, 60 Hz), Europe and North America built in.

⚡ 3D Three-Phase Lab: Generator, Lines, Wye or Delta Load and Meters

Line voltage V_L (L1–L2)
—
Phase voltage
—
Line current I_L (L1)
—
Phase current
—
Neutral current I_N
—
Wattmeter W1
—
Wattmeter W2
—
Real power P
—
Reactive power Q
—
Apparent power S
—
Power factor
—
Rotor angle ωt
—
🧭 Phasor diagram (RMS phasors; voltages and currents have separate scales)
📈 Waveforms (the yellow line is the present instant)
📋 Every phase, as phasors
📐 Power triangle & power-factor correction
—

Scenarios

Supply

Connection (source–load)

Load impedance per phase

Faults

Power-factor correction

Show

Ideal source and lines (no internal or line impedance); every number is an exact complex-number (phasor) calculation, RMS values. Colors: L1 red, L2 yellow, L3 blue, N gray; graphs also use solid / dashed / dotted lines. Wattmeters: current coils in L1 and L2, voltage coils to L3.

For teachers

💡This lab was requested by a student in Brazil taking electrotechnics at university. Is there a topic you wish you could see? Request a simulation →

🏷️ Labeled Three-Phase Diagram & Label Quiz

The diagram behind every three-phase exam question: a wye (star) generator with its neutral, three line conductors, a delta load and a single-phase load. Switch between the labeled diagram, a blank one to test your memory, and a quiz where you place each label yourself. You can also download both versions or print a label worksheet.

generatorL1L2L3NAWye (star) source, delta load and a single-phase load (schematic) · scisim.org

    Tap a word, then tap the numbered box it belongs to (on the diagram or in the list below). Tap a filled box to take the word back. On a phone, swipe the diagram sideways to see every number.

    Download:

    🧮 Problem Generator: Random Three-Phase Problems with Worked Solutions

    New numbers every time. Solve on paper, type your answer for the quantity asked, then open the step-by-step solution.

    🎮 Quiz: Three-Phase Power

    Three-phase quiz

    Fifteen questions (from a bank of twenty), numeric and conceptual: wye and delta, √3, neutral current, power, power factor, capacitor banks and the two-wattmeter method.

    💡 The Idea, Step by Step

    Key idea: three AC voltages of the same size, 120° apart, from one generator. Their currents add up to zero when the load is balanced, so three wires do the work of six, the total power flows steadily instead of pulsing, and the voltage between two lines is √3 times the voltage of one phase.
    Start — why three phases?

    A single AC voltage reaches zero twice every cycle, so the power it delivers pulses: a single-phase motor gets a jerky push. Put three coils round the generator, 120° apart, and the spinning magnet makes three voltages that peak one after another: L1, then L2, then L3. At every moment at least two of them are working, and the total power is perfectly smooth. Because the three currents cancel when the loads are equal, the “return” wire carries nothing and can be thin or left out. In 1891 a three-phase line of roughly 175 km carried power from a hydroelectric plant at Lauffen am Neckar to the International Electrotechnical Exhibition in Frankfurt, one of the first long-distance demonstrations of AC transmission; within a few decades three-phase AC became the standard for power grids.

    Build — wye and delta, and the √3

    The three coils (or loads) can be joined in two ways. In wye (Y, star) one end of each is joined at the star point, which can be connected to a neutral wire. Each coil gets the phase voltage Vph; between two lines you measure the line voltage VL = √3 Vph, because two phasors of the same size 120° apart differ by √3 times that size. That is why Brazil’s 220/380 V supply gives 220 V between a line and neutral and 380 V between two lines (220 × 1.732 = 381). In delta (Δ) the three are joined in a triangle: each one sits between two lines, so Vph = VL, but each line current is the difference of two branch currents, IL = √3 Iph. A delta has no star point, so it has no neutral.

    Deepen — power and power factor

    Each phase has an impedance Z = R + jX. The current lags the phase voltage by the impedance angle φ (inductive load) or leads it (capacitive). Total power: P = √3 VL IL cos φ (watts), Q = √3 VL IL sin φ (var) and S = √3 VL IL (VA), the same formula for wye and delta. The power factor cos φ = P/S tells you how much of the current does useful work. Motors are inductive (PF about 0.8), so they draw extra current that only shuttles energy back and forth. A capacitor bank supplies that reactive power locally: the real power stays the same, but the line current falls, and so do the cable losses and the transformer load.

    University — unbalance, the neutral and measuring power

    With unequal loads the currents no longer cancel. On a 4-wire supply the neutral carries the phasor sum IN = Ia + Ib + Ic and keeps every phase at Vph. Without the neutral, the load’s star point floats to the voltage given by Millman’s theorem, and the phase voltages become unequal: lightly loaded phases get over-voltage. Power in any 3-wire system is measured with just two wattmeters (Blondel): P = W1 + W2. For a balanced load W1 = VLIL cos(30° − φ) and W2 = VLIL cos(30° + φ), so tan φ = √3 (W1 − W2)/(W1 + W2), and W2 goes negative below PF 0.5. Reversing two lines reverses the phase sequence (abc → acb): a motor turns the other way, and the two wattmeter readings swap.

    Try this on the page

    Press Balanced Y, tick Rotate with ωt and watch the phasors spin while the white power curve stays flat. Switch to Same load in Δ: three times the current. Press Unbalanced + neutral, then Broken neutral and watch the lamps. Try PF correction and drag the target to 1.00. Finally press Low PF: a wattmeter reads negative, and the sum is still right.

    📐 Formulas, Derivations & Worked Examples

    QuantityWye (Y, star)Delta (Δ)
    Phase voltage (across one Z)Vph = VL/√3Vph = VL
    Phase current (in one Z)Iph = ILIph = IL/√3
    Phase angle shift (sequence abc)Vab leads Van by 30°Ia lags Iab by 30°
    Neutralpossible (star point); IN = Ia + Ib + Icnone
    Total power (balanced)P = √3 VL IL cos φ = 3 Vph Iph cos φ  ·  Q = √3 VL IL sin φ  ·  S = √3 VL IL  (φ = angle of Z)
    Equivalent impedanceZYZY = ZΔ/3
    Capacitor bank for QCC = QC/(3ωVph²)C = QC/(3ωVL²) = CY/3

    Derivations

    1. Three voltages that add up to zero. The generator gives \(v_a = V_m\cos\omega t\), \(v_b = V_m\cos(\omega t - 120^\circ)\), \(v_c = V_m\cos(\omega t + 120^\circ)\) (sequence abc), with \(V_m = \sqrt2\,V_{ph}\). As RMS phasors, with the operator \(a = 1\angle 120^\circ\): \[V_{an} = V_{ph}\angle 0^\circ,\quad V_{bn} = a^2 V_{an},\quad V_{cn} = a V_{an},\qquad 1 + a + a^2 = 0 \;\Rightarrow\; V_{an}+V_{bn}+V_{cn} = 0.\]
    2. Where the √3 comes from. \[V_{ab} = V_{an} - V_{bn} = V_{ph}\left(1 - 1\angle{-120^\circ}\right) = V_{ph}\left(\tfrac32 + j\tfrac{\sqrt3}{2}\right) = \sqrt3\,V_{ph}\angle 30^\circ.\] Geometry: the tips of Van and Vbn and the star point form an isosceles triangle with two sides Vph and 120° between them; its base is \(2V_{ph}\cos 30^\circ = \sqrt3\,V_{ph}\). The same algebra in a delta, with \(I_{ab} = I_{ph}\angle\theta\) and \(I_{ca} = I_{ph}\angle(\theta + 120^\circ)\), gives \(I_a = I_{ab} - I_{ca} = \sqrt3\,I_{ph}\angle(\theta - 30^\circ)\).
    3. The same power formula for wye and delta. Complex power of the load \(S = \sum_k V_k I_k^{*}\). Balanced: \(P = 3V_{ph}I_{ph}\cos\varphi\). In wye \(V_{ph} = V_L/\sqrt3,\ I_{ph} = I_L\); in delta \(V_{ph} = V_L,\ I_{ph} = I_L/\sqrt3\). Either way \(P = \sqrt3\,V_L I_L\cos\varphi\), where φ is the angle of Z (between phase voltage and phase current). Delta–wye: equal line currents need \(\frac{V_L/\sqrt3}{Z_Y} = \frac{\sqrt3\,V_L}{Z_\Delta}\), so \(Z_Y = Z_\Delta/3\).
    4. Constant instantaneous power. With \(v_k = \sqrt2 V\cos(\omega t + \theta_k)\) and \(i_k = \sqrt2 I\cos(\omega t + \theta_k - \varphi)\): \[p_k = v_k i_k = VI\cos\varphi + VI\cos(2\omega t + 2\theta_k - \varphi).\] For \(\theta_k = 0^\circ, -120^\circ, +120^\circ\) the double-frequency terms are shifted by \(2\theta_k = 0^\circ, -240^\circ, +240^\circ\), again a symmetric set 120° apart, so they add up to zero, so \(p_a + p_b + p_c = 3VI\cos\varphi = P\) at every instant. Watch the white curve in the waveform panel.
    5. Unbalanced loads: the neutral and Millman’s theorem. With a neutral, every load gets its own phase voltage and \(I_N = I_a + I_b + I_c\) (a phasor sum). Without it, Kirchhoff’s current law at the load star point N gives \[V_{Nn} = \frac{V_{an}Y_a + V_{bn}Y_b + V_{cn}Y_c}{Y_a + Y_b + Y_c},\qquad V_{aN} = V_{an} - V_{Nn},\ \text{etc.},\qquad Y_k = 1/Z_k.\] Balanced: \(V_{Nn} = 0\), so the neutral makes no difference. Unbalanced: the star point moves and the phase voltages become unequal.
    6. Power-factor correction. The bank must supply \(Q_C = Q_1 - Q_2 = P(\tan\varphi_1 - \tan\varphi_2)\). Each of the three capacitors supplies \(Q_C/3 = \omega C V^2\), where V is the voltage across it: \[C_Y = \frac{Q_C}{3\,\omega V_{ph}^2},\qquad C_\Delta = \frac{Q_C}{3\,\omega V_L^2} = \frac{C_Y}{3}.\] P does not change; the line current falls from \(P/(\sqrt3 V_L\cos\varphi_1)\) to \(P/(\sqrt3 V_L\cos\varphi_2)\).
    7. Two-wattmeter method (Blondel). In a 3-wire system \(i_c = -i_a - i_b\), so \(p = v_{an}i_a + v_{bn}i_b + v_{cn}i_c = v_{ac}\,i_a + v_{bc}\,i_b\): two meters measure all the power, balanced or not. With current coils in L1 and L2 and voltage coils to L3 (balanced, abc): \[W_1 = \mathrm{Re}\{V_{ac}I_a^{*}\} = V_LI_L\cos(30^\circ - \varphi),\quad W_2 = \mathrm{Re}\{V_{bc}I_b^{*}\} = V_LI_L\cos(30^\circ + \varphi),\] \[W_1 + W_2 = \sqrt3\,V_LI_L\cos\varphi = P,\qquad \tan\varphi = \sqrt3\,\frac{W_1 - W_2}{W_1 + W_2}.\] For a balanced lagging load W2 = 0 at φ = 60° (PF 0.5) and is negative beyond; for a leading (capacitive) load φ < 0 and it is W1 that goes negative below PF 0.5. With sequence acb the two readings swap. With an unbalanced load the formulas for W1, W2 and tan φ no longer apply (a meter can even read negative at a good PF), but P = W1 + W2 still holds. In a 4-wire system with neutral current you need three wattmeters.

    Worked examples (the lab shows the same numbers)

    A. Balanced wye load, 220/380 V, Z = 8 + j6 = 10∠36.87° Ω. Vph = 380/√3 = 219.4 V; IL = 219.4/10 = 21.94 A, lagging Van by 36.87°; PF = 8/10 = 0.80 lagging; P = √3 × 380 × 21.94 × 0.8 = 11.55 kW (check 3 × 21.94² × 8 = 11 552 W); Q = 8.66 kvar; S = 14.44 kVA; IN = 0.
    B. The same impedances in delta. Vph = 380 V; Iph = 380/10 = 38.0 A; IL = √3 × 38 = 65.82 A; P = 3 × 38² × 8 = 34.66 kW, three times the wye value. Equivalent wye: ZΔ/3 = 2.67 + j2 Ω.
    C. Correct example A to PF 0.95 (60 Hz). tan φ1 = 0.75, tan φ2 = tan(arccos 0.95) = 0.3287; QC = 11 552 × 0.4213 = 4.87 kvar. Wye bank: C = 4 867/(3 × 377.0 × 219.4²) = 89.4 µF per phase (delta bank: 29.8 µF). Line current 21.94 A → 11 552/(√3 × 380 × 0.95) = 18.48 A, 16% less.
    D. Unbalanced lamps 10, 20, 40 Ω on 220/380 V. With the neutral: Ia = 21.94∠0°, Ib = 10.97∠−120°, Ic = 5.48∠120° A, so IN = 13.71 − j4.75 = 14.51∠−19.1° A. Without it (Millman): Y = 0.1, 0.05, 0.025 S, VNn = 219.4 × (0.0625 − j0.02165)/0.175 = 82.9∠−19.1° V, and the lamps get 143.6 V, 248.8 V and 287.3 V. The 40 Ω lamp gets 131% of its normal 219.4 V and, as a fixed resistance, 171% of its normal power.
    E. Two wattmeters on example A. W1 = 380 × 21.94 × cos(30° − 36.87°) = 8 277 W; W2 = 380 × 21.94 × cos(66.87°) = 3 275 W; sum 11 552 W = P; tan φ = √3 × 5 002/11 552 = 0.750 → PF 0.80. For Z = 10∠70° Ω instead: W1 = 6 386 W, W2 = −1 448 W, P = 4 939 W.
    F. Open line L3. Wye without neutral: Za and Zb are in series across Vab = 380 V: 190 V and 19.0 A each, Ic = 0. With the neutral, L1 and L2 stay normal (21.94 A) and IN = 21.94 A. Delta: Zab keeps 380 V (38 A), Zbc and Zca share 380 V (19 A); P = 17.33 kW, half of normal.

    Going further

    Why grids use three phases (and not two or six)

    For the same power, the same line-to-line voltage and the same losses, a three-phase 3-wire line needs 75% of the conductor material of a single-phase 2-wire line: each of the three wires carries 1/√3 of the single-phase current, so it can have twice the resistance (half the cross-section). A two-phase system (two voltages 90° apart, used in some early networks) also gives constant power and a rotating field, but needs four wires, or three with an unequal shared wire. Three phases is the smallest symmetric system that does it with three identical wires, which is what makes the simple, rugged induction motor and economical lines possible. More phases add wires without much gain.

    Star–delta starting

    A motor whose windings are rated for the line voltage in delta can be started in wye: each winding then gets VL/√3, so the starting line current is one third of the direct delta start (and the starting torque is one third too). Compare the presets “Balanced Y” (21.94 A) and “Same load in Δ” (65.82 A).

    Supplies around the world

    Brazil uses 60 Hz with low-voltage networks of 127/220 V or 220/380 V, depending on the region and the distribution company. Europe and most IEC countries use 230/400 V, 50 Hz (IEC 60038). North America uses 60 Hz with 120/208 V wye in commercial buildings and 277/480 V in industry (homes get single-phase 120/240 V). The nominal pairs are rounded: 380/√3 = 219.4 V, 400/√3 = 230.9 V. Wire colors: IEC 60445 uses brown, black and gray for L1, L2, L3 and blue for the neutral; this lab draws L1 red, L2 yellow and L3 blue (an older convention still found in many textbooks) because those stay visible on a dark screen, and it names every wire.

    What the model assumes

    Ideal sources and ideal lines (no internal or line impedance), linear loads, sinusoidal steady state, RMS phasors. Lamps are modeled as fixed resistances (a real filament’s resistance rises as it heats up). The wattmeters are ideal and connected on the supply side, so they see the load and the capacitor bank together. A delta source is assumed to have identical windings, so no current circulates inside the delta; its winding currents are then Iab = (Ia − Ib)/3, which is IL/√3 when balanced. The capacitor bank is sized from the load’s own P and Q (for an unbalanced load the corrected PF is then approximate). The animation is slowed down: the real rotor of a 2-pole 60 Hz machine turns 3 600 times a minute. The meters show 3–4 significant figures because the model is exact; real instruments are typically accurate to about 0.5–2%.

    References: C. K. Alexander & M. N. O. Sadiku, Fundamentals of Electric Circuits, chapter “Three-Phase Circuits” (balanced Y–Y, Y–Δ, Δ–Δ, Δ–Y connections, power, unbalanced systems, two-wattmeter method); J. W. Nilsson & S. A. Riedel, Electric Circuits, chapter “Balanced Three-Phase Circuits”; IEC 60038 (standard voltages); IEC 60445 (identification of conductors by colors).
    Model notes: every number is computed in tp_model.js by nodal analysis with complex numbers (Van = Vph∠0° for a wye source; Vab = VL∠0° for a delta source; sequence abc unless acb is chosen) and checked against the hand calculations above in an automated test.

    ❓ FAQ

    Basics What is three-phase power?►

    Three-phase power is AC delivered as three voltages of the same size and frequency, 120 degrees apart, made by three coils in one generator. It is used for almost all generation and transmission and for motors and large loads, because it delivers constant power, needs less conductor material than single-phase for the same power, and produces a rotating magnetic field that drives induction motors.

    Key takeaway: three equal AC voltages 120° apart.
    Basics Why is the line voltage √3 times the phase voltage?►

    In a wye connection the line voltage is the difference of two phase voltages that are 120 degrees apart. Two phasors of size V with 120 degrees between them differ by √3 × V (the base of an isosceles triangle with a 120 degree apex is 2V cos 30° = √3 V). So 220 V phase-to-neutral gives 220 × 1.732 = 380 V between two lines, and the line voltage leads the phase voltage by 30 degrees.

    Key takeaway: V_L = √3 V_ph in wye, from 120° phasor geometry.
    Basics What is the difference between a wye (star) and a delta connection?►

    In wye, one end of each winding or load is joined at a star point that can be connected to a neutral wire; each one gets the phase voltage V_L/√3 and carries the line current. In delta, the three are joined in a triangle, each across two lines: each gets the full line voltage, and the line current is √3 times the branch current. A delta has no neutral point.

    Key takeaway: wye: V_ph = V_L/√3, I_L = I_ph; delta: V_ph = V_L, I_L = √3 I_ph.
    Conceptual Why does the neutral of a balanced three-phase system carry no current?►

    The neutral current is the phasor sum of the three line currents. In a balanced system they are equal in size and 120 degrees apart, and three such phasors add up to zero at every instant. That is why high-voltage transmission lines need only three conductors.

    Key takeaway: balanced currents cancel: I_a + I_b + I_c = 0.
    Conceptual What happens if the neutral breaks while the loads are unbalanced?►

    The star point of the load is no longer held at the supply neutral. It moves to the voltage given by Millman’s theorem, and the phase voltages become unequal. In the lab, lamps of 10, 20 and 40 ohms on a 220/380 V supply get 143.6, 248.8 and 287.3 V instead of 219.4 V: the most lightly loaded phase gets an over-voltage that can destroy appliances. That is why the neutral must never be fused or switched on its own.

    Key takeaway: a lost neutral makes the phase voltages unequal.
    Applied How do you calculate the power of a three-phase load?►

    For a balanced load P = √3 × V_L × I_L × cos φ, Q = √3 × V_L × I_L × sin φ and S = √3 × V_L × I_L, for both wye and delta. Here φ is the angle of the load impedance, the angle between the phase voltage and the phase current, not between line voltage and line current. Example: 380 V, 21.94 A, PF 0.8 gives P = 11.55 kW.

    Key takeaway: P = √3 V_L I_L cos φ, with φ the impedance angle.
    Applied How do you size a capacitor bank for power-factor correction?►

    Find the reactive power to remove, Q_C = P (tan φ1 − tan φ2), then share it between three capacitors: C = Q_C / (3 ω V²), with V the voltage across each capacitor (V_ph for a wye bank, V_L for a delta bank, so a delta bank needs one third of the capacitance). Raising an 11.55 kW load from PF 0.80 to 0.95 at 220/380 V, 60 Hz needs 4.87 kvar: 89.4 µF per phase in wye, and the line current falls from 21.94 A to 18.48 A.

    Key takeaway: Q_C = P(tan φ1 − tan φ2), C = Q_C/(3ωV²).
    Applied What is the two-wattmeter method and why can one wattmeter read negative?►

    In any 3-wire system two wattmeters measure the total power: current coils in two lines, voltage coils to the third, and P = W1 + W2 (Blondel’s theorem). For a balanced load W1 = V_L I_L cos(30° − φ) and W2 = V_L I_L cos(30° + φ). For a lagging load with φ more than 60 degrees (power factor below 0.5), cos(30° + φ) is negative, so W2 reads negative (for a leading load it is W1). The meter is fine; add the readings with their signs. The power factor follows from tan φ = √3 (W1 − W2)/(W1 + W2).

    Key takeaway: P = W1 + W2 with signs; one reading is negative when PF < 0.5.
    Deep Why is the total instantaneous power of a balanced system constant, and why does it matter?►

    The power of each phase is p = VI cos φ plus a term at twice the supply frequency. The three double-frequency terms are shifted by 240 degrees from each other and cancel, so p_a + p_b + p_c = 3 V I cos φ at every instant. A three-phase motor therefore gets a smooth torque without the 100 or 120 Hz pulsation of a single-phase machine, which means less vibration and noise.

    Key takeaway: balanced three-phase power does not pulsate.
    Deep Which three-phase voltages are used in Brazil, Europe and North America?►

    Brazil uses 60 Hz with low-voltage networks of 127/220 V or 220/380 V, depending on the region (the first number is phase-to-neutral, the second line-to-line). Europe and most IEC countries use 230/400 V at 50 Hz. North America uses 60 Hz with 120/208 V in commercial buildings and 277/480 V in industry. All of them are wye systems with V_L = √3 V_ph.

    Key takeaway: Brazil 127/220 or 220/380 V, 60 Hz; Europe 230/400 V, 50 Hz.

    ⚠️ Misconceptions & Common Errors

    ❌ "The line voltage is 3 times the phase voltage."✅ In a wye system V_L = √3 V_ph (1.732 times, not 3): 220 V phase gives 380 V line. The phase voltages are 120° apart, so they do not simply add.🔍 Tick “Line V” in the phasor diagram: the triangle side is √3 times the radius.
    ❌ "The neutral always carries current."✅ In a balanced system the three currents add up to zero, so the neutral carries nothing. It only carries the unbalance current, the phasor sum I_a + I_b + I_c.🔍 Press Balanced Y: A_N reads 0.00 A; then Unbalanced + neutral.
    ❌ "Three phases need six wires."✅ Three separate single-phase circuits would need six wires, but the three return currents cancel, so they can share one wire, and for a balanced load even that wire can be left out: three wires are enough.🔍 Turn the neutral off in Balanced Y: nothing changes.
    ❌ "A delta connection has a neutral."✅ A delta has no star point: each impedance sits between two lines. A neutral is only available from a wye. (A delta source gives V_L only; to supply 127 V or 220 V loads you need a wye winding, e.g. a delta–wye transformer.)🔍 Choose Y–Δ or Δ–Y: the neutral switch is grayed out.
    ❌ "Power factor is the same as efficiency."✅ Power factor is P/S: how much of the current does real work. Efficiency is useful output power over input power. A motor can be 95% efficient at PF 0.8. A low PF does not waste energy in the load itself; it makes the lines carry extra current, which causes extra losses in the cables and transformers.🔍 In PF correction, P stays at 11.55 kW while the current falls.
    ❌ "A negative wattmeter reading means the meter is broken."✅ In the two-wattmeter method W2 = V_L I_L cos(30° + φ) is negative whenever a balanced lagging load has a power factor below 0.5 (for a leading load W1 goes negative instead). The total power is the algebraic sum P = W1 + W2.🔍 Press Low PF: W2 < 0 and W1 + W2 = P.
    How to use these: each wrong idea comes with a check you can do in the lab in a few seconds. The first two and the last are the classic exam traps in three-phase circuits; the formulas behind every correction are derived in the Formulas section above (see also the three-phase chapters of Alexander & Sadiku and Nilsson & Riedel).